Skip to product information
1 of 3

10106/2/1

Brand: Honeywell
Order Number: 10106/2/1
Type: Digital Input Module
Country: USA
Low stock: 100 left

Description

Caret Down

Overview

  • Model: 10106/2/1

  • Type: Fail-Safe Line-Monitored Digital Input Module

  • Brand: Honeywell

  • Application: Digital input with earth fault monitoring, 16 channels

Electrical Specifications

  • Power Requirements:

    • 5 Vdc, 160 mA

    • 24 Vdc, 110 mA

  • Input Resistance: Typically 0.5 MΩ (–40V < U < 40V)

  • Test Current: Typically 0.5 mA

  • Output Voltage: Typically 0.5 Vdc

  • Field Fault Voltage: Max. 250 Vac

Input Details

  • Number of Input Channels: 16

  • Input Type: According to DIN 19234 (NAMUR)

  • Switch Level: 1.4 to 1.9 mA

  • Hysteresis: 0.2 mA ± 0.05 mA

  • Field Wire Resistance: Max. 50 Ω

  • 8 V Loop Supply:

    • Output Voltage: 7.9 to 8.7 V

    • Output Current: 170 mA (short-circuit proof)

Safety Features

  • Earth Connection Monitor: 1

  • Safety Class: AK1-6

Certifications

  • Approvals: CE, UL, TÜV, FM

Software

  • Minimum Version: ≥ 510

Physical Dimensions

  • Space Requirements: 4 TE, 3 HE (4 HP, 3U)